        Fire Doors are Fundamental to comply with the required regulations for buildings

        Follow the below simplified checklist to make sure your customers' fire door hardware is compliant.
        Please refer to Document B of The Building Regulations 2010 (Fire Safety) for the full regulations.

        1

        HINGES

        1. Are there a minimum of 3 hinges with all screws fitted?
        2. Are all the screws the correct size?
        3. Are the hinges free of metal fragments and oil leakage which could be signs of wear?
        4. Are the hinges marked with a CE stamp? Check the grade of the hinge is correct for the door.
        5. If the hinges squeak when the door closes they must be replaced.
        6. Fit the top hinge 200mm from the top of the door and the middle hinge 250mm further down from the centre point of the top hinge and the bottom hinge 200mm from the bottom of the door.
        7. Check that intumescent pads have been fitted in the correct material.
        View Range
        2

        SIGNS

        1. If the door has a closer, does the door display the correct signage on both sides?
        2. Check the correct signage has been fitted to the door and is in accordance with BS5499.
        View Range
        3

        HOLD OPEN DEVICES
        e.g. DORGARD

        1. Does the hold open device release the door when required?
        2. Is the hold open device flashing or beeping? If yes, when were the batteries last changed?
        3. Check the device has been tested in accordance with EN1155 for electromechanical devices.
        View Range
        4

        DOOR CLOSERS

        1. Open the door to 5 degrees or 75mm. Does it close and engage the latch?
        2. Is the closer free from damage and not leaking?
        3. It's recommended that a minimum of power size 3 should be used and the closer must be CE marked.
        4. Check that the closing time of the door is no longer than 25 seconds.
        5. It must be tested and CE marked in the position it is fitted.
        6. If a concealed overhead door closer is used it must also be fitted with the correct intumescent material.
        View Range
        5

        LOCKS & LATCHES

        1. Does the latch hold the door firmly in place without rattling?
        2. Is the lock fitted with the correct intumescent?
        3. Are they CE marked?
        View Range
        6

        SEALS & VISION PANELS

        1. Timber fire doors must have intumescent material fitted.
        2. Are the intumescent seals in place?
        3. If your seal looks like picture A or B, is it free from damage or breakage?
        4. Is the seal continuous around the hardware and fitted correctly into its rebate?
        5. Are the intumescent glazing seals free from damage and tested to BS 476 Pt22?
        6. Vision Panels in doors are needed where doors on escape routes sub-divide corridors
        View Range of Intumescent Strips View Range of Intumescent Glazing Seals View Range of Vision Panels

        Do you need a printable copy to assess multiple fire doors?

        Download the Checklist

        Order replacement firedoor hardware by 8pm for next day delivery.

        Door Closers

        View This Range

        Dorgard Fire Door Holder

        View This Range

        Fire Door Hinges

        View This Range

        Locks and Latches

        View This Range

        Intumescent Strips

        View This Range

        Glazing Seals

        View This Range

        Vision Panels

        View This Range
        Share the checklist with a customer or colleague
        For free advice on fire door products contact the masters by email at sales@ironmongerydirect.com or by phone on 0808 168 22 88 (included in your mobile minutes)
        Contact Us for Free Advice about Fire Doors

        Disclaimer: Whilst every effort has been made to ensure the accuracy of advice given, IronmongeryDirect cannot accept liability for loss or damage arising from the use of the information supplied in this checklist